1. The Plant will be suitable for treating transformer oil by first heating it & then passing it through specially designed filters and then subjecting it to vacuum treatment, which dehydrates and degassifies the oil to following specification.
Parameters Before After Processing
Processing
Break Down Voltage 20kV >65 kV.
Moisture Content 100 PPM <5 PPM
Particle Size Many Micron 1 Micron
Gas Content in
Percentage by vol 10% by Vol. < 0.1%
Oil filtration will be designed for HIGH VACUUM – LOW TEMPERATURE processing of oil for achieving better results.
2. The plant will generally conform to IS-6034-1989 and its latest revision.
3. The oil filtration plant will be designed for high vacuum and low temperature of oil for achieving required results
The plant offered will be mobile type mounted on four pneumatic wheels. The plant will be weatherproof. The casing will be provided with doors of MS sheets hinged on fabricated frame work. Angles and channels to have access to operational Controls and Inspection window etc. The equipment will be enclosed and protected against climatic conditions.
All the component will have adequate strength & rigidity to with stand normal condition of handling transport & usage will be free from edge or corners to avoid injury to operating personal in normal condition of use the design of the plant will be such that if required the parts can easily be replaced.