KYN28-12 Metal-clad indoor movable switchgear

价格 RM100.00对比
发货 AsiaChina付款后24小时内
销量 暂无
评价 已有 0 条评价
人气 已有 0 人关注
数量
+-
库存100件   起订1件
 
联系方式
加关注0

Jiangsu Aokai Electric Co., Ltd

Personal第1年
资料通过认证
保证金未缴纳
  • Asia-China
  • 上次登录 07-08 15:07
  • aokeyelec (Mr.)  

KYN28-12 indoor communication metal armoured open switchgear(hereinatter referred to as the switchgear), department ofthree-phase ac50hz single busbar and double bus section system of indoor complete sets of power distribution equipment, applicable to power plants, substations, and industial and mining enterprises of rated voltage 3.6~12kv power grid, as acceptance and distribution of electrical energy, and the circuit implementation ofcontrol, protection and monitoring.Switch cabinet can be used both domestic well-known brand vacuum circuit breaker(VS¹series, for example), and can choose the intermational well-known brand vacuum circuit breaker(such as ABB VD4 series, the series of Siemens 3ae, schneider company HVX series), can also beinstaled isolation devices or below 12 kv vacuum contactor, complete sets of equipment can meet the requirements of power grid forhigh voltage switchgear, and is suitable for "ive prevention"and the full process, fuly enclosed, the insulation condition, it isa kind of superior performance ofthe power distribution device.

High-voltage Switchgear Use Conditions

1. Ambient temperature: upper limit+40℃, lowerlimit-25℃;

2. Altitude: not higher than 1000m;

3. Relative humidity: daily averagerelative humidity not over 95%, monthly average relative humidity notover 90%;

4. Earthquake strength: not surpass8degree;

5. Locations where no obvious fire or explosive danger, not heavily polluted, no corrosion.

Technical Parameters

Item

Unit

Data

Rated voltage

KV

3, 6, 10

Max. working voltage

KV

3, 6, 7, 2, 12

Rated insulation level

Power-frequency withstand voltage 1min

KV

42

lightning impulse voltage

KV

75

Rated frequency

Hz

50

Rated current ofmain bus

A

6301250, 1600, 2000, 2500, 3150, 4000

Rated current of branch bus

A

630, 1250, 1600, 2000, 2500, 3150, 4000

Thermal Stable Current 3s(effective Value)

KA

16, 20, 25, 31. 5, 40, 50

Rated dynamic stable current(peak)

KA

40, 50, 63, 80, 100, 125

Degree Of Protection

IP4X, 、IP2XEnclosureisIP 4X, whenthe door is open, the inter-comp- artment and the circuit breaker compartment are IP 2X.

 